| Sign In | Join Free | My infospaceinc.com |
|
Application : HVAC, Condensing Unit, Cold Room, Rack System
Model Number : SRC-S(W)-985,SRC-S-985-L4
Packaging Details : WOODEN CASE
Displacement 50/60Hz : 1100/1320 m3/hr
MOQ : 1
Delivery Time : 1 Month
Payment Terms : Western Union,T/T
Refrigerant : R22, R407C, R410a, R404A, R507A
Certification : CE
Oil Charge : 25L
Brand Name : Refcomp
Rated Power : 300HP/224KW
Place of Origin : China
Price : Discussed
Supply Ability : 100000Pcs/Year
| Model | SRC-S(W)-985 | SRC-S-985-L4 |
|---|---|---|
| Rated power | 300HP / 224KW | |
| Exhaust volume (50Hz / 60Hz) | 1100 / 1320 m³/hr | |
| Refrigerant Type | R22, R407C, R410a, R404A, R507A | |
| Weight | 1400 KG | |
| Oil Charge | 25 L | |
| Voltage | 400/3/50Hz – 460/3/60Hz | |
| Cooling Capacity Regulation | 100%, 75%, 50%, 25% (stepless 100%–25%) | |
| LRA Y/Δ | 1062 / 3186 A | 1062 / 3186 A |
A: Engineers must determine the required cooling duty, operating evaporating and condensing temperatures, targeted refrigerant, mains electrical supply parameters, and economizer subcooling requirements.
A: Pre-heat the crankcase via the 275W electrical heater before startup to drive off absorbed refrigerant, verify correct phase sequence rotation, and ensure the oil level is clearly visible in the sight glass.
A: The module constantly reads resistance from six series-connected PTC sensors inside the motor coils and discharge gas chamber, instantly tripping the safety circuit if thermal thresholds are breached.
A: Regularly log operating oil pressure differentials, inspect oil clarity through the sight glass, verify suction filter pressure drop, and test lubricant quality periodically for thermal breakdown or contamination.
|
|