| Sign In | Join Free | My infospaceinc.com |
|
Oil Charge : 19L
Model Number : SRC-S(W)-553,SRC-S-553-L4
Refrigerant : R22, R407C, R410a, R404A, R507A
MOQ : 1
Delivery Time : 1 Month
Packaging Details : WOODEN CASE
Payment Terms : Western Union,T/T
Application : HVAC, Condensing Unit, Cold Room, Rack System
Place of Origin : China
Rated Power : 200HP/150KW
Certification : CE
Displacement 50/60Hz : 600/720 m3/hr
Brand Name : Refcomp
Price : Discussed
Supply Ability : 100000Pcs/Year
| Model | SRC-S(W)-553 | SRC-S-553-L4 |
|---|---|---|
| Rated power | 200HP / 150KW | |
| Exhaust volume (50Hz / 60Hz) | 600 / 720 m³/hr | |
| Refrigerant Type | R22, R407C, R410a, R404A, R507A | |
| Weight | 1030 KG | |
| Oil Charge | 19 L | |
| Voltage | 400/3/50Hz – 460/3/60Hz | |
| Cooling Capacity Regulation | 100%, 75%, 50%, 25% (stepless 100%–25%) | |
| LRA Y/Δ | 543 / 1645A | 595 / 1802A |
A: Piping must match the 105.5 mm (4-1/8") suction line and 80.0 mm (3-1/8") discharge connection to prevent pressure drops and ensure smooth refrigerant flow.
A: The hydraulic slide valve shifts via solenoid valves to provide stepped control at 100%, 75%, 50%, and 25%, or continuous stepless modulation across the 100% to 25% range.
A: Verify that the 275W crankcase heater has been energized to evaporate liquid refrigerant, check phase rotation sequence, and confirm proper wiring of the INT69 SNY protection module.
A: Regularly monitor oil level visibility through the sight glass, inspect suction strainer cleanliness, and periodically test lubricant viscosity and acidity.
|
|
Refcomp SRC-S(W)-553 SRC-S-553-L4 Refrigeration Screw Compressor for HVAC Cold Room Images |